In the FusionModule2000 refrigeration system, which of the following is the optional temperature control type? (Multiple choice)
- A . Half cabinet 25kW air cooling
- B . Half cabinet 30kW water cooling
- C . Row level chilled water 65kW
- D . Full cabinet 42kW air cooling
On the ECC800-Pro WebUl, which of the following is the first-level menu of the NMS Application?
- A . System Settings
- B . Maintenance
- C . Home
- D . Monitoring
When configuring temperature control products, if the temperature of the project location is -10 -30 °C, which of the following working conditions should be preferred?
- A . Wide temperature (-40-55 ℃ )
- B . T1 (-20°-45°C)
- C . T3 (-20-55 ℃ )
- D . Ultra-low temperature (-40-45 ℃ )
Which of the following methods can be used to open the access control for the FusionModule2000 smart module?
- A . Fingerprint
- B . Card reader
- C . Password
- D . Facial recognition
When will the bypass module of Huawei integrated UPS start to work?
- A . Both the active and standby ECMs are abnormal.
- B . The power module overload times out.
- C . The UPS wors in ECO mode, and the bypass voltage is within the preset range
- D . The UPS is just powered on and the inverter is not started.
When the single cell voltage in the battery pack reaches ( ), it means that the battery pack is already in a risky state. (Fill in the blank)
- A . 1.67V
The UPS can generate large leakage currents. A circuit breaker equipped with a residual current device (RCD) is not recommended. If leakage protection is required, consider the leakage current of the UPS and downstream devices.
- A . True
- B . False
Huawei Neteco network management supports mobile APP management.
- A . True
- B . False
Regarding the cabinet rPDU of FusionModule2000, which of the following statements is false?
- A . There are half height and full height
- B . Smart rPDU supports remote monitoring, but does not support remote shutdown
- C . Support C13 and C19 and national standard sockets